PMID- 35677415 OWN - NLM STAT- PubMed-not-MEDLINE LR - 20220609 IS - 2405-8440 (Print) IS - 2405-8440 (Electronic) IS - 2405-8440 (Linking) VI - 8 IP - 6 DP - 2022 Jun TI - Distributed generation adverse impact on the distribution networks protection and its mitigation. PG - e09624 LID - 10.1016/j.heliyon.2022.e09624 [doi] LID - e09624 AB - Integration of Distributed Generation (DG) generates problems for the protection of Distribution Networks (DNs) in power systems. When DG is integrated into a power distribution system (DS), the radial nature of the network is altered and the power starts to flow in a reverse direction. In addition to the reverse flow of power, the DG upsurges the fault current level and affects the existing time intermission coordination of the protective overcurrent relay. This study proposes a reverse power relay (RPR) and Fault Current Limiter (FCL) to mitigate the fault current level and reverse power flow in a Distribution Network (DN) by the use of DG. The FCL works only as a unidirectional fault current limiter (UFCL) by restricting the flow of fault current that occurs in the main grid (MG) of the DG. However, FCLs can protect the flow of fault currents from the MG by affecting the operational flexibility and reliability of the DG. To overcome the flow of fault current of the DG, this study proposes RPR to monitor the power flow to the DG. Collectively the study focuses on the protection of radial DS by using RPR and UFCL. The analysis and the modeling were conducted on the 15KV DN of the radial feeder in Debre Markos DN. The 3Phi fault analysis (which is more severe than others) was performed to validate the protection capability of the mitigation techniques which were proposed in this study. CI - (c) 2022 The Author(s). FAU - Takele, Haymanot AU - Takele H AD - School of Electrical and Computer Engineering, Debre Markos University, Debre Markos, Ethiopia. LA - eng PT - Journal Article DEP - 20220531 PL - England TA - Heliyon JT - Heliyon JID - 101672560 PMC - PMC9167981 OTO - NOTNLM OT - Distributed generation OT - Protection of distribution network OT - Reverse power relay OT - Unidirectional fault current limiter COIS- The authors declare no conflict of interest. EDAT- 2022/06/10 06:00 MHDA- 2022/06/10 06:01 PMCR- 2022/05/31 CRDT- 2022/06/09 02:14 PHST- 2021/11/11 00:00 [received] PHST- 2022/03/02 00:00 [revised] PHST- 2022/05/26 00:00 [accepted] PHST- 2022/06/09 02:14 [entrez] PHST- 2022/06/10 06:00 [pubmed] PHST- 2022/06/10 06:01 [medline] PHST- 2022/05/31 00:00 [pmc-release] AID - S2405-8440(22)00912-4 [pii] AID - e09624 [pii] AID - 10.1016/j.heliyon.2022.e09624 [doi] PST - epublish SO - Heliyon. 2022 May 31;8(6):e09624. doi: 10.1016/j.heliyon.2022.e09624. eCollection 2022 Jun.